Product Model
T6S 1000 PR221DS-LS/I In=1000 3p F F

Selling Points
- 1High Performance: Designed for demanding industrial applications with a rated current of 1000 A.
- 2Solid-State Release: Utilizes advanced solid-state technology for reliable and efficient operation.
- 3Compliance with IEC Standards: Meets stringent IEC standards ensuring safety and reliability.
- 4Electrical Durability: Withstands up to 4000 cycles at 60 cycles per hour, ensuring long-lasting performance.
- 5Versatile Compatibility: Suitable for various operational voltages from 220 V AC to 690 V AC.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 210 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 9.5 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 4000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 50 W | Rated Current (In) | 1000 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 16.5 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA | Rated Uninterrupted Current (Iu) | 1000 A |
Release | PR221DS-LS/I | Release Type | EL |
Short-Circuit Performance Level | S | Standards | IEC |
Sub-type | T6 | Terminal Connection Type | Fixed Circuit-Breakers Front |
Test Voltage Max (Utest) | 3500 V | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA060547R1 |
Specifications may be subject to change without notice