Product Model

T6S 630 BREAKING PART 4p F F

In Stock
Last updated: 2025/4/18
ABB T6S 630 BREAKING PART 4p F F

Selling Points

  • 1Rated Ultimate Short-Circuit Breaking Capacity (Icu) of 630 A.
  • 2Suitable for 4-pole applications with front terminals and thermomagnetic release.
  • 3Electrical durability of 7000 cycles at 60 cycles per hour.
  • 4Compatible with various voltage ranges, including 690 V AC and 750 V DC.
  • 5Meets IEC standards for enhanced safety and performance.
Product Details
T6S 630 BREAKING PART 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK10103A1058 9AKK108467A6707
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
10.5 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable For
T6
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 16.5 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 7.6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 45 kA (500 V AC) 35 kA (690 V AC) 22 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 2 Poles in Series 35 kA (750 V DC) 3 Poles in Series 20 kA
Rated Uninterrupted Current (Iu)
630 A
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060332R1

Specifications may be subject to change without notice