Product Model
T6V 630 BREAKING PART 3p F F

Selling Points
- 1Rated Ultimate Short-Circuit Breaking Capacity (Icu) of 630 A.
- 2Advanced EL release type for reliable operation.
- 3Withstands 20000 cycles at 120 cycles per hour.
- 4Suitable for moulded case circuit breakers and fixed circuit-breakers.
- 5Meets IEC standards and CE declaration of conformity.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 210 mm |
Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
Product Net Weight | 8.2 kg | Product Main Type | SACE Tmax T |
Product Name | Moulded Case Circuit Breaker | Product Type | Breaking Part |
Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3P |
Power Loss | at Rated Operating Conditions per Pole 30.6 W | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC 750 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 65 kA (690 V AC) 30 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 7.6 kA |
Rated Uninterrupted Current (Iu) | 630 A | Short-Circuit Performance Level | V |
Standards | IEC | Sub-type | T6 |
Terminal Connection Type | Fixed Circuit-Breakers Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA069437R1 |
Specifications may be subject to change without notice