Product Model
TAL26-30-10RT 17-32V DC

Selling Points
- 1Reliable Operation: Designed for consistent performance in 17-32V DC environments.
- 2Versatile Applications: Suitable for controlling power circuits, motors, isolation, capacitor switching, and lighting.
- 3Efficient Design: Fitted with low consumption DC coils and a wide coil voltage range.
- 4Durable Construction: 3-pole contactor with a block-type design and built-in auxiliary contact.
- 5Wide Compatibility: Compatible with various industrial applications and control systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 54 mm | Product Net Depth / Length | 110.6 mm |
Product Net Height | 90 mm | Product Net Weight | 0.75 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V | Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 45 A acc. to IEC 60947-5-1, Π= 40 °C 16 A | Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 45 A (690 V) 55 °C 40 A (690 V) 70 °C 32 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 26 A (440 V) 55 °C 26 A (500 V) 55 °C 22 A (690 V) 55 °C 13 A (380 / 400 V) 55 °C 26 A (220 / 230 / 240 V) 55 °C 26 A | Rated Operational Power AC-3 (Pe) | (415 V) 11 kW (440 V) 15 kW (500 V) 15 kW (690 V) 11 kW (380 / 400 V) 11 kW (220 / 230 / 240 V) 6.5 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A | Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 50 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 210 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 45 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 90 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 110 A for 0.1 s 140 A for 1 s 100 A | Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-2 / AC-4) 300 cycles per hour (AC-3) 1200 cycles per hour | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 1.1 A / 121 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Mechanical Durability | 10 million | Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | DC Operation 17 ... 32 V | Coil Consumption | Holding DC (Umin / Umax) 2.7 / 9 W Pull-in DC (Umin / Umax) 2.7 / 9 W |
Operate Time | Between Coil De-energization and NO Contact Opening 12 ... 18 ms Between Coil Energization and NO Contact Closing 55 ... 110 ms | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Connecting Capacity Main Circuit | Flexible with Cable Lug 1 ... 6 mm² Rigid Cable 1 ... 6 mm² |
Connecting Capacity Auxiliary Circuit | Rigid or Flexible with Cable Lug 0.75 ... 2.5 mm² | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Connecting Terminals (delivered in open position) Main Poles | M 4 (+,-) pozidriv 2 screw with conic washer | Terminal Type | Ring-Tongue Terminals |
General Use Rating UL/CSA | (600 V AC) 40 A | Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 7-1/2 hp (220 ... 240 V AC) Three Phase 10 hp (440 ... 480 V AC) Three Phase 20 hp (550 ... 600 V AC) Three Phase 25 hp |
Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 55 °C Close to Contactor without Thermal O/L Relay (Ucmin-Ucmax) according to IEC 60077 -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C | Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 20 g Closed, Shock Direction: B1 15 g Closed, Shock Direction: C1 20 g Closed, Shock Direction: C2 14 g Open, Shock Direction: A 10 g Open, Shock Direction: B1 5 g Open, Shock Direction: C1 8 g Open, Shock Direction: C2 8 g Shock Direction: B2 10 g |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4756 >> Capacitor magnet contactor | Manufacturer ID | 1SBL243060R5110 |
Specifications may be subject to change without notice