Product Model
TAL30-30-10 17-32V DC

Selling Points
- 1High Insulation Voltage: Up to 1000 V according to IEC 60947-4-1 and VDE 0110 (Gr. C).
- 2Robust Design: Meets IEC 60529 and EN 60529 standards for IP20 auxiliary terminals.
- 3Wide Operating Range: Operates between -25°C to +55°C close to the contactor and -60°C to +80°C for storage.
- 4Flexible Installation: Front and side-mounted add-on auxiliary contact blocks available.
- 5Energy Efficiency: Low consumption DC coils with a large coil voltage range.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 54 mm | Product Net Depth / Length | 125.3 mm |
Product Net Height | 90 mm | Product Net Weight | 0.85 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V | Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 65 A acc. to IEC 60947-5-1, Π= 40 °C 16 A | Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 55 A (690 V) 55 °C 55 A (690 V) 70 °C 39 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 32 A (440 V) 55 °C 32 A (500 V) 55 °C 28 A (690 V) 55 °C 18 A (380 / 400 V) 55 °C 32 A (220 / 230 / 240 V) 55 °C 33 A | Rated Operational Power AC-3 (Pe) | (415 V) 15 kW (440 V) 18.5 kW (500 V) 18.5 kW (690 V) 15 kW (380 / 400 V) 15 kW (220 / 230 / 240 V) 9 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A | Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 63 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 65 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A for 0.1 s 140 A for 1 s 100 A | Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 470 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 175 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-2 / AC-4) 300 cycles per hour (AC-3) 1200 cycles per hour | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 0.55 A / 60 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Mechanical Durability | 10 million | Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | DC Operation 17 ... 32 V | Coil Consumption | Holding DC (Umin / Umax) 2.7 / 9 W Pull-in DC (Umin / Umax) 2.7 / 9 W |
Operate Time | Between Coil De-energization and NO Contact Opening 12 ... 18 ms Between Coil Energization and NO Contact Closing 55 ... 110 ms | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Connecting Capacity Main Circuit | Flexible with Cable End 2.5 ... 10 mm² Rigid Cable 2.5 ... 16 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
Connecting Terminals (delivered in open position) Main Poles | M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector | Terminal Type | Screw Terminals |
General Use Rating UL/CSA | (600 V AC) 50 A | Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 10 hp (220 ... 240 V AC) Three Phase 10 hp (440 ... 480 V AC) Three Phase 25 hp (550 ... 600 V AC) Three Phase 30 hp |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C Close to Contactor without Thermal O/L Relay -40 ... 55 °C Close to Contactor without Thermal O/L Relay (Ucmin-Ucmax) according to IEC 60077 -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C | Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 20 g Closed, Shock Direction: B1 15 g Closed, Shock Direction: C1 20 g Closed, Shock Direction: C2 14 g Open, Shock Direction: A 10 g Open, Shock Direction: B1 5 g Open, Shock Direction: C1 8 g Open, Shock Direction: C2 8 g Shock Direction: B2 10 g |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
Manufacturer ID | 1SBL283061R5110 |
Specifications may be subject to change without notice