Product Model

UA16-30-10RA 110-115V 50Hz / 115-127V 60Hz

In Stock
Last updated: 2025/4/19
ABB UA16-30-10RA 110-115V 50Hz / 115-127V 60Hz

Selling Points

  • 1High Peak Current Handling: Handles peak currents far exceeding 100 times nominal RMS current.
  • 2Durable Construction: Delivered complete with damping resistors, ensuring reliable operation without additional inductances.
  • 3Safety Features: Capacitors must be discharged to ≤50V before re-energizing to prevent electrical shock.
  • 4Long Operating Cycles: Electrical durability of 250,000 operating cycles for Ue <500V and 100,000 cycles for 500V ≤ Ue ≤ 690V.
  • 5Versatile Application: Suitable for various installations requiring capacitor switching, ensuring efficient energy management.
Product Details
UA16-30-10RA 110-115V 50Hz / 115-127V 60Hz
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
44 mm
Product Net Depth / Length
107 mm
Product Net Height
120 mm
Product Net Weight
0.46 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Power AC-6b (Pe)
(230 / 240 V) 40 °C, 50 / 60 Hz 8 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 7.5 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 6 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 12.5 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 10 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 12.5 kvar (440 V) 40 °C, 50 / 60 Hz 15 kvar (440 V) 55 °C, 50 / 60 Hz 13 kvar (440 V) 70 °C, 50 / 60 Hz 11 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 18 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 16 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 12.5 kvar (690 V) 40 °C, 50 / 60 Hz 22 kvar (690 V) 55 °C, 50 / 60 Hz 21 kvar (690 V) 70 °C, 50 / 60 Hz 17 kvar
Rated Operational Current AC-15 (Ie)
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Short-Circuit Protective Devices
Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 80 A
Rated Short-time Withstand Current Low Voltage (Icw)
for 0.1 s 140 A for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Maximum Electrical Switching Frequency
240 cycles per hour
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 1.1 A / 121 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Control Circuit Voltage (Uc)
50 Hz 110 ... 115 V 60 Hz 115 ... 127 V
Coil Consumption
Average Holding Value 50 Hz 8 V·A Average Holding Value 60 Hz 8 V·A Average Pull-in Value 50 Hz 70 V·A Average Pull-in Value 60 Hz 80 V·A
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Cable End 1x 0.75 ... 2.5 mm² Rigid Solid 1x 1 ... 4 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Cable End 1/2x 0.75 ... 2.5 mm² Rigid Solid 1/2x 1 ... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Connecting Terminals (delivered in open position) Main Poles
M 3.5 (+,-) pozidriv 2 screws with cable clamp
Terminal Type
Screw Terminals
Connecting Capacity Main Circuit UL/CSA
1x 18-10 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb Control Circuit 9 in·lb Main Circuit 9 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Object Classification Code
Q
ETIM 7
EC001079 - Capacitor contactor
ETIM 8
EC001079 - Capacitor contactor
ETIM 9
EC001079 - Capacitor contactor
eClass
V11.0 : 27371006
UNSPSC
39121529
Manufacturer ID
1SBL181024R8910

Specifications may be subject to change without notice