Product Model
UA26-30-01RA 220-230V50HZ

Selling Points
- 1High Peak Current Handling: Handles peak currents exceeding 100 times nominal rms current.
- 2Durable Design: Electrical durability of 250,000 cycles for Ue < 500 V and 100,000 cycles for 500 V ≤ Ue ≤ 690 V.
- 3Integrated Damping Resistors: Includes built-in damping resistors to limit current peaks during capacitor switching.
- 4Versatile Connectivity: Compatible with rigid and flexible cables, with M4 and M3.5 pozidriv screw terminals.
- 5Compliant with International Standards: Meets IEC 60947-4-1 and IEC 60947-5-1 standards for safety and performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 45 mm | Product Net Depth / Length | 87.3 mm |
Product Net Height | 90 mm | Product Net Weight | 0.71 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 0 | Number of Auxiliary Contacts NC | 1 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1 | Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 12 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 11 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 8.5 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 20 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 14.5 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 18.5 kvar (440 V) 40 °C, 50 / 60 Hz 22 kvar (440 V) 55 °C, 50 / 60 Hz 20 kvar (440 V) 70 °C, 50 / 60 Hz 16 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 22 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 22 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 19.5 kvar (690 V) 40 °C, 50 / 60 Hz 30 kvar (690 V) 55 °C, 50 / 60 Hz 30 kvar (690 V) 70 °C, 50 / 60 Hz 25 kvar |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A | Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 1.1 A / 121 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V 60 Hz 230 ... 240 V | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
Terminal Type | Screw Terminals | Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C |
Maximum Operating Altitude Permissible | Without Derating 3000 m | ETIM 7 | EC001079 - Capacitor contactor |
ETIM 8 | EC001079 - Capacitor contactor | ETIM 9 | EC001079 - Capacitor contactor |
eClass | V11.0 : 27371006 | UNSPSC | 39121529 |
Manufacturer ID | 1SBL241024R8001 |
Specifications may be subject to change without notice