Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 54 mm | Product Net Depth / Length | 108.3 mm |
Product Net Height | 90 mm | Product Net Weight | 0.71 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 0 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1 | Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Π= 40 °C 16 A |
Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 16 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 16 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 27.5 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 19 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 27.5 kvar (440 V) 40 °C, 50 / 60 Hz 30 kvar (440 V) 55 °C, 50 / 60 Hz 30 kvar (440 V) 70 °C, 50 / 60 Hz 20 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 34 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 34 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 23.5 kvar (690 V) 40 °C, 50 / 60 Hz 45 kvar (690 V) 55 °C, 50 / 60 Hz 45 kvar (690 V) 70 °C, 50 / 60 Hz 32 kvar | Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A |
Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 1.5 ... 1.8 A | Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 1.1 A / 121 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Mechanical Durability | 10 million | Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz 200 V 60 Hz 200 ... 220 V | Coil Consumption | Average Holding Value 50 Hz 12 V·A Average Holding Value 60 Hz 12 V·A Average Pull-in Value 50 Hz 120 V·A Average Pull-in Value 60 Hz 140 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 3 W Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 3 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 120 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 140 V·A |
Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 8 ... 21 ms | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Connecting Capacity Main Circuit | Flexible with Cable End 2.5 ... 10 mm² Rigid Cable 2.5 ... 16 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
Connecting Terminals (delivered in open position) Main Poles | M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector | Terminal Type | Screw Terminals |
Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C | Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Object Classification Code | Q |
ETIM 7 | EC001079 - Capacitor contactor | ETIM 8 | EC001079 - Capacitor contactor |
ETIM 9 | EC001079 - Capacitor contactor | eClass | V11.0 : 27371006 |
UNSPSC | 39121529 | Manufacturer ID | 1SBL281022R7510 |