Product Model

UA63-30-00RA 200V 50Hz / 200-220V 60Hz

In Stock
Last updated: 2025/4/19
ABB UA63-30-00RA 200V 50Hz / 200-220V 60Hz

Selling Points

  • 1High Peak Current Handling: Handles peak currents exceeding 100 times nominal rms current.
  • 2Durable Design: Electrical durability of 250,000 operating cycles for Ue < 500 V and 100,000 cycles for 500 V ≤ Ue ≤ 690 V.
  • 3Capacitor Precharging: Ensures capacitor precharging to limit second current peak upon making of main poles.
  • 4IP20 Enclosure: Meets IEC 60529 and IEC 60947-1 standards for degree of protection.
  • 5Wide Operating Range: Operates at 50 Hz (200-220 V) and 60 Hz (200-220 V), suitable for various frequency applications.
Product Details
UA63-30-00RA 200V 50Hz / 200-220V 60Hz
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
70 mm
Product Net Depth / Length
140.4 mm
Product Net Height
150 mm
Product Net Weight
1.35 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz
Rated Operational Power AC-6b (Pe)
(230 / 240 V) 40 °C, 50 / 60 Hz 30 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 27 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 23 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 50 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 39 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 45 kvar (440 V) 40 °C, 50 / 60 Hz 55 kvar (440 V) 55 °C, 50 / 60 Hz 48 kvar (440 V) 70 °C, 50 / 60 Hz 42.5 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 65 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 60 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 50 kvar (690 V) 40 °C, 50 / 60 Hz 80 kvar (690 V) 55 °C, 50 / 60 Hz 75 kvar (690 V) 70 °C, 50 / 60 Hz 65 kvar
Short-Circuit Protective Devices
gG Type Fuses 200 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Maximum Electrical Switching Frequency
240 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Control Circuit Voltage (Uc)
50 Hz 200 V 60 Hz 200 ... 220 V
Coil Consumption
Average Holding Value 50 Hz 18 V·A Average Holding Value 60 Hz 18 V·A Average Pull-in Value 50 Hz 180 V·A Average Pull-in Value 60 Hz 210 V·A
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 8 ... 27 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH75-25 (75 x 25 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Cable End 6 ... 10 mm² Rigid Cable 6 ... 16 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting Terminals (delivered in open position) Main Poles
M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
Terminal Type
Screw Terminals
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Object Classification Code
Q
ETIM 7
EC001079 - Capacitor contactor
ETIM 8
EC001079 - Capacitor contactor
ETIM 9
EC001079 - Capacitor contactor
eClass
V11.0 : 27371006
UNSPSC
39121529
Manufacturer ID
1SBL371024R7500

Specifications may be subject to change without notice