Product Model
UAF95-30-00RA-72

Selling Points
- 1High Peak Current Capacity: Handles peak currents 100 times the nominal RMS current.
- 2Robust Design: Meets IEC 60529 and IEC 60947-1 standards for durability and protection.
- 3Versatile Operation: Operates with control voltages between 20-60 V DC.
- 4Capacitor Switching Ready: Designed for capacitor switching applications with high reliability.
- 5Flexible Connectivity: Supports flexible and rigid cable connections with M8 hexagon socket screws.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 90 mm | Product Net Depth / Length | 155.6 mm |
Product Net Height | 170 mm | Product Net Weight | 1.8 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 0 | Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Main Circuit 1000 V | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 145 A |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 145 A (690 V) 55 °C 135 A (690 V) 70 °C 115 A | Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 96 A (440 V) 55 °C 93 A (500 V) 55 °C 80 A (690 V) 55 °C 65 A (1000 V) 55 °C 30 A (380 / 400 V) 55 °C 96 A (220 / 230 / 240 V) 55 °C 96 |
Rated Operational Power AC-3 (Pe) | (380 / 400 V) 45 kW | Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 35 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 35 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 30 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 65 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 55 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 65 kvar (440 V) 40 °C, 50 / 60 Hz 65 kvar (440 V) 55 °C, 50 / 60 Hz 65 kvar (440 V) 70 °C, 50 / 60 Hz 55 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 70 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 70 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 60 kvar (690 V) 40 °C, 50 / 60 Hz 80 kvar (690 V) 55 °C, 50 / 60 Hz 80 kvar (690 V) 70 °C, 50 / 60 Hz 70 kvar |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A | Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
Mechanical Durability | 10 million | Maximum Mechanical Switching Frequency | 300 cycles per hour |
Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ⤠70 °C) | Rated Control Circuit Voltage (Uc) | DC Operation 20 ... 60 V |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A Holding at Max. Rated Control Circuit Voltage DC 2 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 350 V·A Pull-in at Max. Rated Control Circuit Voltage DC 400 V·A | Operate Time | Between Coil De-energization and NC Contact Closing 60 ... 130 ms Between Coil De-energization and NO Contact Opening 55 ... 125 ms Between Coil Energization and NC Contact Opening 27 ... 77 ms Between Coil Energization and NO Contact Closing 30 ... 80 ms |
Connecting Capacity Main Circuit | Bar 30 mm² Flexible with Cable End 1 x 10 ... 70 mm² Rigid 2 x 6 ... 65 mm² | Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 1 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm² |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | Connecting Terminals (delivered in open position) Main Poles | M8 hexagon socket screw with single connector |
Terminal Type | Cable Clamp | Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 30 hp (208 V AC) Three Phase 30 hp (220 ... 240 V AC) Three Phase 30 hp (440 ... 480 V AC) Three Phase 60 hp (550 ... 600 V AC) Three Phase 75 hp | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Shock acc. to IEC 60068-2-27 | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g |
Object Classification Code | Q | ETIM 7 | EC001079 - Capacitor contactor |
ETIM 8 | EC001079 - Capacitor contactor | ETIM 9 | EC001079 - Capacitor contactor |
eClass | V11.0 : 27371006 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4756 >> Capacitor magnet contactor | Manufacturer ID | 1SFL437024R7200 |
Specifications may be subject to change without notice