Product Model
XT1C160 TMD40/450 FFC 4P

Selling Points
- 1Handles short-circuit currents up to 450 A.
- 2Withstands 8000 electrical cycles and 25000 mechanical cycles.
- 3Measuring 76.2 mm in width, 130 mm in height, and 70 mm in depth.
- 4Ensures reliable operation with TMD release type.
- 5Easy installation with front terminal connections.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 2.6 W |
Rated Current (In) | 40 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | TMD |
Release Type | TM | Short-Circuit Performance Level | C |
Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT1 |
Terminal Connection Type | Front for Copper Cables | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 2TFH100063R1001 |
Specifications may be subject to change without notice