Product Model
XT1H 125 MCP In=125 3p F F UL/CSA

Selling Points
- 1High-Performance Motor Protection: Designed to safeguard 3-phase motors with a rated current of 125 A.
- 2Magnetic Release: Ensures reliable operation with a magnetic release mechanism.
- 3UL/CSA Certification: Meets stringent safety standards under UL and CSA regulations.
- 4Energy Management: Ideal for controlling power circuits up to 600Y/347 V AC and 500 V DC.
- 5Durable Design: Built with a moulded case circuit breaker design for long-lasting durability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 76.2 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
Product Net Weight | 1.1 kg | Circuit Breaker Type to be Associated | Motor Protection |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Suitable for Product Class | SACE Tmax XT |
Version | F | CAD Dimensional Drawing | 1SDH001295R0008 |
Connecting Capacity Main Circuit | Busbar 45.5 ... 80 mm² | Current Type | AC/DC |
Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
Number of Poles | 3P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple | 1 piece | Power Loss | at Rated Operating Conditions per Pole 10.3 W |
Rated Current (In) | 125 A | Rated Instantaneous Short-Circuit Current Setting (Ii) | 375â¦1375 A |
Rated Operational Voltage | 600Y/347 V AC 500 V DC | Rated Uninterrupted Current (Iu) | 125 A |
Rated Voltage (Ur) | 600Y/347 V | Recommended Screw Driver | Main Circuit M6 |
Release | MA | Release Type | M |
Short-Circuit Performance Level | H | Standards | UL489 |
Sub-type | XT1 | Terminal Connection Type | Front |
Terminal Type | Bolt | Tightening Torque | 6 N·m |
Interrupting Rating acc. to UL489 | (240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | IDEA Granular Category Code (IGCC) | 4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers |
Object Classification Code | Q | UNSPSC | 39121616 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA074732R1 |
Specifications may be subject to change without notice