Product Model

XT1H 125 TMF 60-600 4p F F UL/CSA

In Stock
Last updated: 2025/4/27
ABB XT1H 125 TMF 60-600 4p F F UL/CSA

Selling Points

  • 1High Performance: Designed for reliable operation in demanding power distribution environments.
  • 2UL and CSA Certified: Meets stringent safety standards for UL and CSA certifications.
  • 3Thermal-Magnetic Release: Features a TMF release for efficient and safe operation.
  • 4Four Poles: Suitable for four-pole applications, ensuring comprehensive circuit protection.
  • 5Durable Construction: Built with robust materials for long-lasting performance and minimal maintenance.
Product Details
XT1H 125 TMF 60-600 4p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 3.9 W
Rated Current (In)
60 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
600 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
60 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074717R1

Specifications may be subject to change without notice