Product Model

XT1H160 TMD50/500 PMP 3P

In Stock
Last updated: 2025/4/28
ABB XT1H160 TMD50/500 PMP 3P

Selling Points

  • 1High Performance: Designed to handle short-circuit currents up to 100 kA at 220/230 V AC.
  • 2Reliable Operation: Features a thermal-magnetic release (TMD) for reliable operation in various voltage conditions.
  • 3Front Terminal Connection: Easy installation with front terminal connections for efficient wiring.
  • 4Wide Voltage Range: Compatible with voltages from 50 to 500 V AC, making it versatile for different applications.
  • 5Durable Design: Constructed with high-quality materials to ensure long-lasting durability and mechanical stability.
Product Details
XT1H160 TMD50/500 PMP 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 5.0 W
Rated Current (In)
50 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 75 kA (230 V AC) 75 kA (240 V AC) 75 kA (380 V AC) 52.5 kA (415 V AC) 37.5 kA (440 V AC) 32.5 kA (500 V AC) 25 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 52.5 kA (500 V DC) 3 Poles in Series 52.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 35 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100555R1001

Specifications may be subject to change without notice