Product Model
XT1N 160 TMF 16-450 3p F F

Selling Points
- 1High current capacity of 160 A for efficient power handling.
- 2Thermomagnetic release (TMF) ensures safe and reliable operation.
- 3Front terminal connection (F) for easy installation and maintenance.
- 4Meets IEC standards for electrical durability and safety.
- 5Compact dimensions (76.2 mm x 130 mm x 70 mm) for space-saving installations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 76.2 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
Product Net Weight | 1 kg | Circuit Breaker Type to be Associated | Power Distribution |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH001295R0008 | Current Type | AC/DC |
Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
Number of Poles | 3P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple | 1 piece | Rated Current (In) | 16 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Instantaneous Short-Circuit Current Setting (Ii) | 450 A |
Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V |
Release | TMF | Release Type | TM |
Setting Range | 16 A | Short-Circuit Performance Level | N |
Standards | IEC60947-2 | Sub-type | XT1 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA080827R1 |
Specifications may be subject to change without notice