Product Model
XT1S 160 TMD 40-450 4p F F

Selling Points
- 1High Breaking Capacity: 50 kA for reliable performance.
- 2Thermomagnetic Release: Ensures safe and efficient operation.
- 3IEC Standards Compliance: Meets international safety and performance standards.
- 4Adjustable Type: Suitable for various industrial settings.
- 5Front Terminal Design: Easy installation and maintenance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 101.6 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
Product Net Weight | 1.3 kg | Circuit Breaker Type to be Associated | Power Distribution |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH001295R0080 | Current Type | AC/DC |
Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
Number of Poles | 4 | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple | 1 piece | Rated Current (In) | 40 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Instantaneous Short-Circuit Current Setting (Ii) | 450 A |
Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V |
Release | TMD | Release Type | TM |
Setting Range | 28...40 A | Short-Circuit Performance Level | S |
Standards | IEC60947-2 | Sub-type | XT1 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA080849R1 |
Specifications may be subject to change without notice