Product Model
XT2H160 MA52/314-728 PMP 3P

Selling Points
- 170KA for efficient circuit protection.
- 2Ensures safe and reliable operation.
- 3Suitable for 3-phase applications.
- 4Compatible with 400VAC and 690VAC.
- 5Built to withstand demanding electrical environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | P | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 3P | Rated Current (In) | 52 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA | Rated Uninterrupted Current (Iu) | 160 A |
Release | MA | Release Type | M |
Remarks | ATLAS | Short-Circuit Performance Level | H |
Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT2 |
Terminal Connection Type | Plug-In Circuit-Breakers | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 2TFH100668R1001 |
Specifications may be subject to change without notice