Product Model
XT2H160 TMA63/630 WMP 3P

Selling Points
- 1Handles up to 100 kA at 220 V AC and 70 kA at 380 V AC.
- 2Ensures reliable and fast operation with a release time of 15 ms.
- 3Convenient and secure connection points for easy installation.
- 4Rated for 63 A to 315 A, suitable for various electrical applications.
- 5Meets IEC standards for power circuit-breakers, ensuring global compatibility.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | W | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 5.7 W |
Rated Current (In) | 63 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | TMA |
Release Type | TM | Remarks | ATLAS |
Short-Circuit Performance Level | H | Standards | IEC60947-2 GB/T 14028.2 |
Sub-type | XT2 | Terminal Connection Type | Withdrawable Circuit-Breakers |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH102086R1001 |
Specifications may be subject to change without notice