Product Model
XT2L 160 Ekip Dip LIG In=25A 4p F F

Selling Points
- 1High Current Capacity: Handles up to 25A with a robust solid-state release mechanism.
- 2Reliable AC Power Distribution: Ensures uninterrupted operation with a short-circuit breaking capacity of 150 kA at 220-240 V AC.
- 3Robust Insulation: Withstands 690 V AC and 500 V DC, providing excellent electrical durability.
- 4Compact Design: Measures 120 mm in width, 82.5 mm in height, and 130 mm in depth, making it ideal for space-constrained applications.
- 5Compliance with IEC Standards: Meets IEC 60947 standards for safety and performance, ensuring high reliability in electrical installations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 120.0 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.6 kg | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Current Type | AC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 0.8 W |
Rated Current (In) | 25 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | Ekip Dip LIG |
Release Type | EL | Short-Circuit Performance Level | L |
Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT2 |
Terminal Connection Type | Front | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 2TFN000066A1001 |
Specifications may be subject to change without notice