Product Model
XT2L 160 Ekip Dip LSIG In=10A 4p F F

Selling Points
- 1Advanced Protection: Equipped with electronic trip units for precise overload and short-circuit protection.
- 2Adjustable Settings: Allows for customizable trip settings to suit various application requirements.
- 3High Breaking Capacity: Capable of breaking short circuits up to 150kA at 240Vac.
- 4Durable Design: Built to withstand 8000 operations with load and 25000 operations at no load.
- 5Compact Dimensions: Measuring H130mm x W120mm x D82.5mm for easy installation in tight spaces.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 120 mm | Product Net Height | 130 mm |
Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.6 kg |
Circuit Breaker Type to be Associated | Power Distribution | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | CAD Dimensional Drawing | 1SDH002230A1002 |
Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
Power Loss | at Rated Operating Conditions per Pole 0.10 W | Rated Current (In) | 10 A |
Rated Frequency (f) | 50/60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V AC | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA |
Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V AC |
Release | Ekip Dip LSIG | Release Type | EL |
Short-Circuit Performance Level | L | Standards | IEC |
Sub-type | XT2 | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SDA122942R1 |
Specifications may be subject to change without notice