Product Model

XT2N 160 Ekip Dip LSI In=160A 4p F F In=100%

In Stock
Last updated: 2025/4/21
ABB XT2N 160 Ekip Dip LSI In=160A 4p F F In=100%

Selling Points

  • 1High Performance: Designed to meet any installation requirement, even the most critical ones.
  • 2Advanced Protection: Integrates extra functionalities into a standard moulded case circuit breaker with advanced protection functions and logics.
  • 3Reliable Operation: Offers 8000 operations under electrical load and 25000 operations at no load for mechanical durability.
  • 4Versatile Accessories: Compatible with one-fits-all accessories and intuitive design for fast upgrades and customization.
  • 5Compliance Standards: Meets IEC 60947-1 and IEC 60947-2 standards, ensuring compliance with global electrical safety regulations.
Product Details
XT2N 160 Ekip Dip LSI In=160A 4p F F In=100%
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA100019R1

Specifications may be subject to change without notice