ABB XT2N 160 Ekip Touch Measuring LSI In=40A 4p F F

Selling Points

  • 1Features Ekip Touch technology for enhanced reliability and precision.
  • 2Rated for up to 65 kA at 220V AC and 10 kA at 690V AC.
  • 3Available in fixed four-pole configuration with front terminals.
  • 4Includes measuring capabilities for precise monitoring and control.
  • 5Meets IEC 60947-2 standards for safety and performance.
Product Details
XT2N 160 Ekip Touch Measuring LSI In=40A 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch Measuring LSI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFN000162A1001

Specifications may be subject to change without notice