Product Model
XT2N160 TMA100/1000 PMP 4P

Selling Points
- 1Rated up to 65 kA at 220 V AC and 36 kA at 380 V AC.
- 2Ensures reliable operation with a thermomagnetic release mechanism.
- 3Suitable for a variety of applications with its four-pole configuration.
- 4Meets international standards for electrical safety and performance.
- 5Built to withstand 8000 cycles of electrical durability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | P | Current Type | AC/DC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 4 | Power Loss | at Rated Operating Conditions per Pole 9.5 W |
Rated Current (In) | 100 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC 500 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | TMA |
Release Type | TM | Remarks | ATLAS |
Short-Circuit Performance Level | N | Standards | IEC60947-2 GB/T 14028.2 |
Sub-type | XT2 | Terminal Connection Type | Plug-In Circuit-Breakers |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH100975R1001 |
Specifications may be subject to change without notice