Product Model

XT2N160 TMA100/1000 PMP 4P

In Stock
Last updated: 2025/4/19
ABB XT2N160 TMA100/1000 PMP 4P

Selling Points

  • 1Rated up to 65 kA at 220 V AC and 36 kA at 380 V AC.
  • 2Ensures reliable operation with a thermomagnetic release mechanism.
  • 3Suitable for a variety of applications with its four-pole configuration.
  • 4Meets international standards for electrical safety and performance.
  • 5Built to withstand 8000 cycles of electrical durability.
Product Details
XT2N160 TMA100/1000 PMP 4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 9.5 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100975R1001