Product Model
XT2N 160 TMA 160-1600 3p F F

Selling Points
- 1Withstands 120 cycles per hour and 8000 cycles for long-lasting performance.
- 2Easy and secure connection with bolt terminals.
- 3Ensures safe and reliable operation with a fast release time.
- 4Rated for 800 to 1600 A, suitable for various power distribution needs.
- 5Meets IEC standards for safety and performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 90 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.4 kg | Circuit Breaker Type to be Associated | Power Distribution |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH002230A1001 | Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3 |
Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
Power Loss | at Rated Operating Conditions per Pole 16.15 W | Rated Current (In) | 160 A |
Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 800â¦1600 A | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Uninterrupted Current (Iu) | 160 A |
Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M6 |
Release | TMA | Release Type | TM |
Setting Range | 112...160 A | Short-Circuit Performance Level | N |
Standards | IEC60947-2 | Sub-type | XT2 |
Terminal Connection Type | Front | Terminal Type | Bolt |
Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | IDEA Granular Category Code (IGCC) | 4927 >> Molded case circuit breakers |
Object Classification Code | Q | UNSPSC | 39121616 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA067020R1 |
Specifications may be subject to change without notice