Product Model
XT2N 160 TMG 32-160 4p F F

Selling Points
- 1High Performance: Designed for high current applications with a rated current of 160 A.
- 2Reliable Operation: Features a thermomagnetic release (TMG) for reliable short-circuit breaking capacity.
- 3Front Terminal Connection: Easy installation with front terminal connections for efficient wiring.
- 4IEC Compliant: Meets IEC standards for safety and performance in electrical systems.
- 5Compact Design: Compact dimensions of 120 mm x 130 mm x 82.5 mm for space-saving installations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 120 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.45 kg | Circuit Breaker Type to be Associated | Generator Protection |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH002230A1002 | Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
Power Loss | at Rated Operating Conditions per Pole 2.57 W | Rated Current (In) | 32 A |
Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 160 A | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Uninterrupted Current (Iu) | 160 A |
Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M6 |
Release | TMG | Release Type | TM |
Setting Range | 22.4...32 A | Short-Circuit Performance Level | N |
Standards | IEC60947-2 | Sub-type | XT2 |
Terminal Connection Type | Front | Terminal Type | Bolt |
Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA067730R1 |
Specifications may be subject to change without notice