Product Model
XT2S 125 Ekip Dip LSIG In=10A 4p F F UL/CSA

Selling Points
- 1Equipped with electronic trip units for enhanced safety and reliability.
- 2Handles up to 125A with thermal magnetic and electronic trip units.
- 3Supports ring-lug or bar connections for flexible installation options.
- 4Meets UL 489 and CSA C22.2 standards, ensuring compliance with industry regulations.
- 5Trip units can be upgraded via ABB Ability Marketplace for future-proofing and new functionalities.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 120 mm | Product Net Height | 130 mm |
Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.6 kg |
Circuit Breaker Type to be Associated | Power Distribution | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | CAD Dimensional Drawing | 1SDH002230A1002 |
Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
Power Loss | at Rated Operating Conditions per Pole 0.10 W | Rated Current (In) | 10 A |
Rated Frequency (f) | 50/60 Hz | Rated Insulation Voltage (Ui) | 1000 V AC |
Rated Operational Voltage | 690 V AC | Rated Uninterrupted Current (Iu) | 160 A |
Rated Voltage (Ur) | 690 V AC | Release | Ekip Dip LSIG |
Release Type | EL | Short-Circuit Performance Level | S |
Standards | UL | Sub-type | XT2 |
Interrupting Rating acc. to UL489 | (240 V AC) 100 A (480 V AC) 35 A (600 V AC) 22 A | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SDA102122R1 |
Specifications may be subject to change without notice