Product Model

XT2S 160 Ekip Dip LIG In=100A 3p F F

In Stock
Last updated: 2025/4/21
ABB XT2S 160 Ekip Dip LIG In=100A 3p F F

Selling Points

  • 1Withstands 120 cycles per hour and 8000 cycles, ensuring reliable operation in demanding environments.
  • 2Provides fast and efficient short-circuit interruption with an opening time of 15 ms.
  • 3Meets international safety and performance standards for circuit breakers.
  • 4Dimensions: 130 mm width, 145 mm length, and 208 mm height, making it easy to integrate into various systems.
  • 5Certified under WEEE Category V11.1 for environmental sustainability.
Product Details
XT2S 160 Ekip Dip LIG In=100A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.1 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA100043R1

Specifications may be subject to change without notice