Product Model
XT2S 160 Ekip Dip LIG In=160A 3p F F

Selling Points
- 1High Electrical Durability: Withstands up to 25,000 cycles and 8000 hours of operation.
- 2Solid-State Release: Ensures reliable and fast tripping performance.
- 3Front Terminal Connection: Easy installation and maintenance with front terminals.
- 4Wide Voltage Compatibility: Rated for 220-690 V AC with short-circuit breaking capacities up to 85 kA.
- 5Compliance with IEC60947 Standards: Meets international safety and performance standards.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 90 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.642 kg | Circuit Breaker Type to be Associated | Power Distribution |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH002230A1001 | Current Type | AC |
Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
Number of Poles | 3P | Order Multiple | 1 piece |
Power Loss | at Rated Operating Conditions per Pole 16.1 W | Rated Current (In) | 160 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA | Rated Uninterrupted Current (Iu) | 160 A |
Release | Ekip Dip LIG | Release Type | EL |
Short-Circuit Performance Level | S | Standards | IEC60947-2 |
Sub-type | XT2 | Terminal Connection Type | Front |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA100044R1 |
Specifications may be subject to change without notice