Product Model

XT2S 160 Ekip Touch LSI In=40A 3p F F

In Stock
Last updated: 2025/4/23
ABB XT2S 160 Ekip Touch LSI In=40A 3p F F

Selling Points

  • 1Equipped with Ekip Touch and Hi-Touch trip units for enhanced protection against overload and short-circuit.
  • 2Utilize the user-friendly software e-Configure for easy selection and customization of the right products.
  • 3Offers ultimate short-circuit breaking capacity of up to 85kA and service short-circuit breaking capacity of up to 50kA.
  • 4Features a modular structure with one-fits-all accessories, improving the circuit breaker's versatility and sophistication.
  • 5Designed for 8000 operations under electrical load and 25,000 operations at no load, ensuring long-lasting performance.
Product Details
XT2S 160 Ekip Touch LSI In=40A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFN000086A1001

Specifications may be subject to change without notice