Product Model
XT2S 160 Ekip Touch LSI In=63A 3p F F

Selling Points
- 1Advanced Protection: Equipped with Ekip Touch LSI technology for enhanced protection against overload and short-circuit.
- 2High Breaking Capacity: Capable of breaking currents up to 85 kA at 240V AC, ensuring reliable operation under extreme conditions.
- 3Versatile Design: Modular structure with one-fits-all accessories for easy customization and upgradeability.
- 4Energy Efficiency: Meets stringent energy management standards with 1% accuracy certification for trip units.
- 5Compliance and Certifications: Compliant with IEC 60947-1 and 60947-2 standards, as well as EC directives for low voltage and electromagnetic compatibility.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 90.0 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.2 kg | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Current Type | AC |
Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 1.7 W |
Rated Current (In) | 63 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA |
Rated Uninterrupted Current (Iu) | 160 A | Release | Ekip Touch LSI |
Release Type | EL | Short-Circuit Performance Level | S |
Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT2 |
Terminal Connection Type | Front | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 2TFN000087A1001 |
Specifications may be subject to change without notice