XT2V 125 BREAKING PART 4p F F UL/CSA

Selling Points
- 1Compliant with UL/CSA Standards: Meets stringent safety standards for North American markets.
- 2High Current Capacity: Handles up to 125A, ensuring robust performance in demanding applications.
- 34-Pole Configuration: Ideal for systems requiring four poles of protection and control.
- 4Enhanced Safety Features: Includes Ekip Touch LSI for improved safety and reliability.
- 5Durable Construction: Built with high-quality materials for long-lasting performance and minimal maintenance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 120 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 1.2 kg | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Breaking Part |
Suitable for Product Class | SACE Tmax XT | Version | F |
Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
Number of Poles | 4P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
Order Multiple | 1 piece | Rated Operational Voltage | 600 V AC 500 V DC |
Rated Uninterrupted Current (Iu) | 125 A | Rated Voltage (Ur) | 600 V |
Short-Circuit Performance Level | V | Standards | UL489 |
Sub-type | XT2 | Terminal Connection Type | Front |
Interrupting Rating acc. to UL489 | (240 V AC) 200 kA (480 V AC) 150 kA (600 V AC) 42 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA075639R1 |
Specifications may be subject to change without notice