ABB XT2V 125 TMA 125-625..1250 4p FF UL/CSA

Selling Points

  • 1Designed for continuous operation with a mechanical life of 25,000 operations.
  • 2Equipped with TMA trip units for precise protection and control.
  • 3Meets UL and CSA standards for safety and reliability.
  • 4Available in 4-pole configuration for diverse power distribution needs.
  • 5Suitable for applications requiring up to 125A at 600V AC.
Product Details
XT2V 125 TMA 125-625..1250 4p FF UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
625…1250 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
V
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 150 kA (600 V AC) 42 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074872R1

Specifications may be subject to change without notice