Product Model

XT2V 125 TMF 60-600 4p F F UL/CSA

In Stock
Last updated: 2025/4/20
ABB XT2V 125 TMF 60-600 4p F F UL/CSA

Selling Points

  • 1High Voltage Rating: 600 V rated voltage for reliable operation in demanding electrical environments.
  • 2Thermomagnetic Release: Advanced thermomagnetic release mechanism ensures safe and efficient circuit interruption.
  • 3UL and CSA Certified: Meets stringent UL and CSA standards for safety and performance.
  • 4Four-Pole Configuration: Suitable for a variety of electrical applications requiring four-pole connections.
  • 5Front Terminal Design: Easy access to terminals for convenient installation and maintenance.
Product Details
XT2V 125 TMF 60-600 4p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.4 W
Rated Current (In)
60 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
600 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
60 A
Short-Circuit Performance Level
V
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 150 kA (600 V AC) 42 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074866R1

Specifications may be subject to change without notice