Product Model

XT3N 250 MA 160 Im=960...1920 3p F F

In Stock
Last updated: 2025/4/21
ABB XT3N 250 MA 160 Im=960...1920 3p F F

Selling Points

  • 1High Performance: Designed for robust electrical durability with 120 cycles per hour and 8000 cycles.
  • 2Motor Protection: Ideal for motor protection with a rated uninterrupted current of 250 ampere.
  • 3Three-Pole Configuration: Compatible with three-pole configurations, ensuring efficient power distribution.
  • 4Magnetic Release: Equipped with magnetic release for quick and safe operation.
  • 5Compliance with IEC Standards: Meets IEC standards for reliability and safety in industrial settings.
Product Details
XT3N 250 MA 160 Im=960...1920 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.7 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0409
Connecting Capacity Main Circuit
Busbar 85..192 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 7.9 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
960…1920 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 27 kA (415 V AC) 36 kA (440 V AC) 19 kA (500 V AC) 15 kA (525 V AC) 9.75 kA (690 V AC) 3.75 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 20 kA (525 V AC) 13 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
MA
Release Type
M
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT3
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA068073R1

Specifications may be subject to change without notice