Product Model

XT3S 250 TMD 250-2500 3p F F

In Stock
Last updated: 2025/4/22
ABB XT3S 250 TMD 250-2500 3p F F

Selling Points

  • 1High Performance: Designed to handle high currents and short-circuit capacities up to 85 kA.
  • 2Reliability: Features a thermomagnetic release (TMD) for consistent and reliable operation.
  • 3Versatile Application: Suitable for AC/DC power distribution, including 220-690 V AC and 250-500 V DC.
  • 4Advanced Technology: Equipped with front terminals and adjustable trip settings for precise control.
  • 5Durable Construction: Built with robust materials, ensuring long-lasting mechanical durability.
Product Details
XT3S 250 TMD 250-2500 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.7 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0409
Connecting Capacity Main Circuit
Busbar 85..192 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 17.8 W
Rated Current (In)
250 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
2500 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 27 kA (415 V AC) 36 kA (440 V AC) 20 kA (500 V AC) 15 kA (525 V AC) 10 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 27 kA (500 V DC) 3 Poles in Series 37.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
TMD
Release Type
TM
Setting Range
175...250 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT3
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA068221R1

Specifications may be subject to change without notice