Selling Points

  • 1Designed to handle up to 200-600A with a short-circuit breaking capacity of 50kA.
  • 2Equipped with thermomagnetic release (TMG) for enhanced safety and reliability.
  • 3Specifically designed for generator protection, ensuring reliable operation under various conditions.
  • 4Suitable for motor control applications, providing precise and reliable protection.
  • 5Compact dimensions (155mm x 155mm x 190mm) for easy installation in tight spaces.
Product Details
XT3S 250 TMG200/600 P MP 3P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105.0 mm
Product Net Height
150.0 mm
Product Net Depth / Length
70.0 mm
Product Net Weight
3.24 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 15.8 W
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 42.5 kA (230 V AC) 42.5 kA (240 V AC) 42.5 kA (380 V AC) 27 kA (415 V AC) 27 kA (440 V AC) 20 kA (500 V AC) 15 kA (525 V AC) 10 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 37.5 kA (500 V DC) 3 Poles in Series 37.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMG
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT3
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH101343R1001

Specifications may be subject to change without notice