Product Model

XT4N 160 Ekip Dip LIG In=40A 3p F F

In Stock
Last updated: 2025/4/20
ABB XT4N 160 Ekip Dip LIG In=40A 3p F F

Selling Points

  • 1Handles short-circuit currents up to 65 kA.
  • 2Built with solid-state release technology for enhanced reliability.
  • 3Suitable for DIN rail mounting, ideal for space-constrained applications.
  • 4Offers adjustable overload release current setting from 40 to 100 A.
  • 5Meets EU Directive 2011/65/EU and Amendment 2015/863 for environmental compliance.
Product Details
XT4N 160 Ekip Dip LIG In=40A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
105 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.05 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1003
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.6 W
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT4
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA100181R1