Product Model

XT4N 160 Ekip Dip LSIG In=100A 3p F F

In Stock
Last updated: 2025/4/21
ABB XT4N 160 Ekip Dip LSIG In=100A 3p F F

Selling Points

  • 1Designed for AC applications with a solid-state release mechanism for reliable operation.
  • 2Meets IEC standards for safety and performance, ensuring compliance with international electrical regulations.
  • 3Rated at 100A, suitable for a wide range of electrical installations requiring precise current control.
  • 4Three-pole configuration for balanced protection in electrical circuits.
  • 5Built with durable materials and robust design for long-lasting performance in harsh environments.
Product Details
XT4N 160 Ekip Dip LSIG In=100A 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
105 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.5 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1003
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.20 W
Rated Current (In)
100 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 A (230 V AC) 65 A (240 V AC) 65 A (380 V AC) 36 A (415 V AC) 36 A (440 V AC) 36 A (500 V AC) 30 A (525 V AC) 20 A (690 V AC) 10 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 A (230 V AC) 65 A (240 V AC) 65 A (380 V AC) 36 A (415 V AC) 36 A (440 V AC) 36 A (500 V AC) 30 A (525 V AC) 20 A (690 V AC) 10 A
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
XT4
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA100178R1

Specifications may be subject to change without notice