Product Model
XT4N 160 Ekip Dip LSIG In=100A 3p F F

Selling Points
- 1Designed for AC applications with a solid-state release mechanism for reliable operation.
- 2Meets IEC standards for safety and performance, ensuring compliance with international electrical regulations.
- 3Rated at 100A, suitable for a wide range of electrical installations requiring precise current control.
- 4Three-pole configuration for balanced protection in electrical circuits.
- 5Built with durable materials and robust design for long-lasting performance in harsh environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 105 mm | Product Net Height | 160 mm |
Product Net Depth / Length | 82.5 mm | Product Net Weight | 2.5 kg |
Circuit Breaker Type to be Associated | Power Distribution | Product Main Type | SACE Tmax XT |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | CAD Dimensional Drawing | 1SDH002230A1003 |
Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
Power Loss | at Rated Operating Conditions per Pole 4.20 W | Rated Current (In) | 100 A |
Rated Frequency (f) | 50/60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V AC | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 A (230 V AC) 65 A (240 V AC) 65 A (380 V AC) 36 A (415 V AC) 36 A (440 V AC) 36 A (500 V AC) 30 A (525 V AC) 20 A (690 V AC) 10 A | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 A (230 V AC) 65 A (240 V AC) 65 A (380 V AC) 36 A (415 V AC) 36 A (440 V AC) 36 A (500 V AC) 30 A (525 V AC) 20 A (690 V AC) 10 A |
Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V AC |
Release | Ekip Dip LSIG | Release Type | EL |
Short-Circuit Performance Level | N | Standards | IEC |
Sub-type | XT4 | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SDA100178R1 |
Specifications may be subject to change without notice