Product Model

XT4N 160 Ekip LSIG In=40A 4p F F

In Stock
Last updated: 2025/4/27
ABB XT4N 160 Ekip LSIG In=40A 4p F F

Selling Points

  • 1High Electrical Durability: Withstands up to 8000 operations under load and 25000 operations at no load.
  • 2Advanced Protection Functions: Includes L, S, I, and G protection against overload, short-circuit with time delay, instantaneous short-circuit, and earth fault.
  • 3Modular Design: Easy selection and customization with one-fits-all accessories and intuitive e-Configure software.
  • 4Comprehensive Compliance: Meets IEC 60947-1 and IEC 60947-2 standards, as well as EC directives for Low Voltage and Electromagnetic Compatibility.
  • 5Versatile Application: Suitable for a wide range of electrical installations, including transformer and generator protection.
Product Details
XT4N 160 Ekip LSIG In=40A 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0677
Connecting Capacity Main Circuit
Busbar 85..200 mm²
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.60 W
Rated Current (In)
40 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M8
Release
Ekip LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT4
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
Interrupting Rating acc. to UL489
(240 V AC) 65 A (480 V AC) 25 A (600 V AC) 18 A
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA068158R1

Specifications may be subject to change without notice