Product Model
XT4N 160 Ekip LSI In=63A 4p F F

Selling Points
- 1Designed for industrial and tertiary applications, ensuring reliable operation under various conditions.
- 2Engineered with energy efficiency in mind, reducing environmental impact and maximizing power generation.
- 3Compliant with IEC standards and CE certified, ensuring rigorous safety and technical criteria.
- 4Features a solid-state release mechanism for fast and reliable operation.
- 5Equipped with front terminals for easy installation and maintenance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 140 mm |
Product Net Height | 160 mm | Product Net Depth / Length | 82.5 mm |
Product Net Weight | 3.5 kg | Circuit Breaker Type to be Associated | Power Distribution |
Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
Product Type | Automatic Circuit Breaker | Version | F |
CAD Dimensional Drawing | 1SDH001295R0677 | Connecting Capacity Main Circuit | Busbar 85..200 mm² |
Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
Power Loss | at Rated Operating Conditions per Pole 1.40 W | Rated Current (In) | 63 A |
Rated Frequency (f) | 50/60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V AC | Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA |
Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V AC |
Recommended Screw Driver | Main Circuit M8 | Release | Ekip LSI |
Release Type | EL | Short-Circuit Performance Level | N |
Standards | IEC60947-2 | Sub-type | XT4 |
Terminal Connection Type | Front | Terminal Type | Bolt |
Tightening Torque | 8 N·m | Interrupting Rating acc. to UL489 | (240 V AC) 100 A (480 V AC) 35 A (600 V AC) 22 A |
ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q | UNSPSC | 39120000 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA068154R1 |
Specifications may be subject to change without notice