Product Model

XT4N 160 Ekip Touch Measuring LSIG In=160A 4p F F

In Stock
Last updated: 2025/4/27
ABB XT4N 160 Ekip Touch Measuring LSIG In=160A 4p F F

Selling Points

  • 1Equipped with Ekip Touch LSIG trip unit for comprehensive overload, short circuit, and ground fault protection.
  • 2Measures current, voltage, power, energy, power factor, frequency, and THD without external modules or sensors.
  • 3Interchangeable trip units for easy integration into various electrical systems, including power distribution and motor protection.
  • 4Rated for 160A with a short-circuit breaking capacity of up to 36 kA at 380V AC.
  • 5Compact design suitable for DIN rail mounting, enhancing space efficiency in industrial settings.
Product Details
XT4N 160 Ekip Touch Measuring LSIG In=160A 4p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140.0 mm
Product Net Height
160.0 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 8.9 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Touch Measuring LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFN001090A1001

Specifications may be subject to change without notice