Product Model

XT4N 250 TMA 250-2500 4p F F InN=100%

In Stock
Last updated: 2025/4/21
ABB XT4N 250 TMA 250-2500 4p F F InN=100%

Selling Points

  • 1Up to 36 kA at 415 V AC, ensuring robust protection against electrical surges.
  • 2Adjustable trip unit for customizable settings, providing both thermal and magnetic protection.
  • 3Suitable for a wide range of applications including power distribution, transformer, and generator installations.
  • 4Withstands up to 8000 operations under load and 25,000 operations at no load, ensuring long-lasting performance.
  • 5Meets IEC 60947-1 and IEC 60947-2 standards, ensuring compliance with global electrical safety regulations.
Product Details
XT4N 250 TMA 250-2500 4p F F InN=100%
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.872 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0677
Connecting Capacity Main Circuit
Busbar 85..200 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.44 W
Rated Current (In)
250 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250…2500 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
TMA
Release Type
TM
Setting Range
175...250 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT4
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA068111R1