Product Model

spau-v1r-h-q4d-lk-a-m12d

In Stock
Last updated: 2025/4/28
Festo spau-v1r-h-q4d-lk-a-m12d

Selling Points

  • 1Measures relative pressure with 1.5% FS accuracy and 0.3% FS repetition accuracy.
  • 2Compliant with EU EMC Directive, CE marking, and RoHS Directive for safe operation in harsh environments.
  • 3Freely programmable threshold value or window comparator via IO-Link for remote maintenance and parameterization.
  • 4Compatible with latching lock and rotatable screw-type lock, with optional H-rail mounting for flexible installation.
  • 5Measures pressure from 0 MPa to -0.1 MPa, suitable for monitoring compressed air and non-corrosive gases.
Product Details
spau-v1r-h-q4d-lk-a-m12d
Festo

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Symbol
00995412
Certification
RCM compliance mark c UL us - Listed (OL)
CE marking (see declaration of conformity)
As per EU EMC directive As per EU RoHS directive
UKCA marking (see declaration of conformity)
To UK instructions for EMC To UK RoHS instructions
KC characters
KC EMC
Note on materials
RoHS-compliant
Measured variable
Relative pressure
Method of measurement
Piezoresistive pressure sensor
Pressure measuring range initial value
0psi
Pressure measuring range end value
-14.5psi
Overload pressure
72.5psi
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4] Inert gas
Information on operating and pilot media
Operation with oil lubrication possible
Temperature of medium
0°C 50°C
Ambient temperature
0°C 50°C
ADC resolution
12bit
Accuracy in ± % FS
1.5%FS
Repetition accuracy in ± %FS
0.3%FS
Temperature co-efficient in ± %FS/K
0.05%FS/K
Switching output
2xPNP
Switching function
Freely programmable
Switching element function
N/C contact/N/O contact switchable
Max. output current
100mA
Analog output
4 - 20 mA
Rise time
3ms
Max. load resistance of current output
500Ohm
Min. load resistance of voltage output
10kOhm
Short-circuit protection
yes
Protocol
IO-Link?
IO-Link?, protocol version
Device V 1.1
IO-Link?, profile
Smart sensor profile
IO-Link?, function classes
Binary data channel (BDC) Process data variable (PDV) Identification Diagnostics Teach channel
IO-Link?, communication mode
COM2 (38,4 kBd)
IO-Link?, SIO mode support
Yes
IO-Link?, port class
A
IO-Link?, process data width OUT
0 Byte
IO-Link?, process data width IN
2 Byte
IO-Link?, process data content IN
14 bit PDV (pressure measurement) 2 bit BDC (pressure monitoring)
IO-Link?, minimum cycle time
3 ms
IO-Link?, data memory required
500byte
DC operating voltage range
20V 30V
Reverse polarity protection
for all electrical connections
Electrical connection 1, connection type
Plug
Electrical connection 1, connection technology
M12x1 A-coded as per EN 61076-2-101
Electrical connection 1, number of pins/wires
4
Electrical connection 1, type of mounting
Compatible with latching lock Compatible with screw lock rotatable
Electrical connection for input 1, connection pattern
00995386
Type of mounting
With H-rail
Mounting position
Any
Pneumatic connection
QS-4
Product weight
40g
Materials in contact with the media
FPM Brass, nickel-plated NBR PA-reinforced
Display type
LED
Displayable unit(s)
MPa bar inH2O inHg kPa kgf/cm2 mmHg psi
Setting options
IO-Link?
Protection against tampering
IO-Link?
Setting range threshold value
0% 100%
Setting range hysteresis
0% 90%
Degree of protection
IP65 IP67
Corrosion resistance class (CRC)
2 - Moderate corrosion stress
LABS (PWIS) conformity
VDMA24364-B1/B2-L
Manufacturer ID
8003352

Specifications may be subject to change without notice