Festo spte-p10r-q4-v-2.5k

Selling Points

  • 1High Accuracy: Measures relative pressure with an accuracy of 3% of full scale.
  • 2Versatile Applications: Suitable for HVAC systems, gas cylinders, air pumps, and other pneumatic equipment.
  • 3Rapid Readings: Provides near-instantaneous readings with a rise time of 1ms.
  • 4Robust Design: Features a durable PA-reinforced housing resistant to wear, abrasion, and chemical damage.
  • 5Easy Installation: Practical push-in connections make it easy to link to pneumatic equipment.
Product Details
spte-p10r-q4-v-2.5k
Festo

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Symbol
00992257
Certification
RCM compliance mark c UL us - Recognized (OL)
CE marking (see declaration of conformity)
As per EU EMC directive As per EU RoHS directive
UKCA marking (see declaration of conformity)
To UK instructions for EMC To UK RoHS instructions
Certificate issuing authority
UL E322346
Note on materials
RoHS-compliant
Measured variable
Relative pressure
Method of measurement
Piezoresistive pressure sensor
Pressure measuring range initial value
0psi
Pressure measuring range end value
145psi
Overload pressure
217.5psi
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4]
Information on operating and pilot media
Operation with oil lubrication possible
Temperature of medium
0°C 50°C
Ambient temperature
0°C 50°C
Accuracy in ± % FS
3%FS
Repetition accuracy in ± %FS
0.3%FS
Temperature co-efficient in ± %FS/K
0.05%FS/K
Analog output
0 - 10 V
Rise time
1ms
Min. load resistance of voltage output
15kOhm
Short-circuit protection
For all electrical connections
DC operating voltage range
18V 30V
Reverse polarity protection
for all electrical connections
Electrical connection
3-wire Cable Open end
Cable length
2.5m
Type of mounting
With accessories
Mounting position
Any
Pneumatic connection
QS-4
Product weight
35g
Housing material
PA-reinforced
Sealing ring material
FPM NBR
Degree of protection
IP40
Corrosion resistance class (CRC)
2 - Moderate corrosion stress
LABS (PWIS) conformity
VDMA24364-B2-L
Cleanroom class
Class 4 according to ISO 14644-1
Manufacturer ID
571487

Specifications may be subject to change without notice