Product Model
vppm-8f-l-1-f-0l6h-lk-s1

Selling Points
- 1Regulates pressure accurately within 0.006 MPa to 0.6 MPa.
- 2Ensures reliable and long-lasting operation with soft sealing.
- 3Supports direct connection to higher-order IO-Link/I-Port masters for seamless communication.
- 4Easy to operate with electrical actuation for precise control.
- 5Meets IP65 protection standards and operates in temperatures from 0°C to 60°C.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Nominal width pressurization | 8mm | Exhaust nominal width | 7mm |
Actuation type | Electrical | Sealing principle | Soft |
Mounting position | Any | Structural design | Pilot-controlled diaphragm regulator |
Short-circuit protection | For all electrical connections | Safety instructions | VPPM safety position: if the supply cable breaks, the outlet pressure is maintained in uncontrolled form. |
Symbol | 00995303 | Reverse polarity protection | for all electrical connections |
Reset method | Mechanical spring | Type of control | Pilot-controlled |
Valve function | 3-way proportional pressure control valve | Display type | LED |
Pressure regulation range MPa | 0.006MPa 0.6MPa | Pressure regulation range | 0.06bar 6bar |
Inlet pressure 1 | 0bar 8bar | Inlet pressure 1 MPa | 0MPa 0.8MPa |
Max. pressure hysteresis | 0.03bar | Standard nominal flow rate | 1050l/min |
DC operating voltage range | 18V 30V | Max. current consumption | 300mA |
Duty cycle | 100% | Max. electrical power consumption | 7W |
Protocol | I-Port IO-Link? | Residual ripple | 10 % |
Operating medium | Compressed air as per ISO 8573-1:2010 [7:4:4] Inert gas | Information on operating and pilot media | Operation with oil lubrication not possible |
Certification | RCM compliance mark c UL us - Listed (OL) | KC characters | KC EMC |
CE marking (see declaration of conformity) | As per EU EMC directive As per EU RoHS directive | UKCA marking (see declaration of conformity) | To UK instructions for EMC To UK RoHS instructions |
Certificate issuing authority | UL E322346 | Corrosion resistance class (CRC) | 2 - Moderate corrosion stress |
LABS (PWIS) conformity | VDMA24364-B1/B2-L | Temperature of medium | 10°C 50°C |
Degree of protection | IP65 | Ambient temperature | 0°C 60°C |
Product weight | 560g | Linearity | 1%FS |
Hysteresis | 0.5%FS | Reproducibility | 0.5%FS |
Overall accuracy | 1.25 %FS | Temperature coefficient | 0.04%/K |
Repetition accuracy FS | 0.5% | IO-Link?, protocol version | Device V 1.1 |
IO-Link?, communication mode | COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd) | IO-Link?, port class | A |
IO-Link?, process data width OUT | 2 Byte | IO-Link?, process data width IN | 2 Byte |
IO-Link?, minimum cycle time | 0.5 ms | Type of mounting | Optionally: With through-hole With accessories |
Pneumatic connection 1 | Sub-base | Pneumatic connection 2 | Sub-base |
Pneumatic connection 3 | Sub-base | Note on materials | RoHS-compliant |
Housing material | Wrought aluminum alloy Anodized | Manufacturer ID | 8031111 |
Specifications may be subject to change without notice