Festo vsnc

Selling Points

  • 1Innovative Design: The VSNC valves are pilot valves for single- and double-acting quarter turn and linear actuators, meeting VDI/VDE 3845 standards.
  • 2Customizable Options: Configurable product with various options available, including different voltage and pressure settings.
  • 3High Reliability: Designed for process automation with a mechanical spring for single solenoid valves and protective caps for armature tube exhaust.
  • 4Explosion Protection: Meets IEC Ex standards for zone 1 to IEC Ex with type of ignition protection Ex-ia, Ex-mb, and Ex-nA.
  • 5Versatile Mounting: Can be mounted on actuators without a NAMUR interface using appropriate accessories like connection sets.
Product Details
vsnc
Festo

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Valve function
5/2, bistable 5/2 or 3/2 switchable 5/3, pressurized 5/3, exhausted 5/3, closed
Actuation type
Electrical
Width
32mm
Standard nominal flow rate
800l/min 1350l/min
Pneumatic working port
NAMUR connection diagram
Operating voltage
110V AC 120V AC 12V DC 230V AC 240V AC 24V AC 24V DC 48V AC 48V DC Via solenoid coil, to be ordered separately
Operating pressure
1.5bar 10bar
Structural design
Piston gate valve Plate seat
Reset method
Mechanical spring
Certification
c UL us - Recognized (OL)
CE marking (see declaration of conformity)
as per EU explosion protection directive (ATEX) As per EU low voltage directive
Explosion protection certification outside the EU
Class I, Div. 1 (US) Class I, Div. 2 (US) Class II, Div. 1 (US) Class II, Div. 2 (US) Class III, Div. 1 (US) Class III, Div. 2 (US) EPL Da (IEC-EX) EPL Db (IEC-EX) EPL Db (KR) EPL Dc (KR) EPL Ga (IEC-EX) EPL Ga (KR) EPL Gb (IEC-EX) EPL Gb (KR) EPL Gc (KR)
Certificate issuing authority
DNVGL-TAA000011J
ATEX category gas
II 2G II 3G
ATEX category for dust
II 2D II 3D
Type of ignition protection for gas
AEx m II T4 Ex db IIC T4 Gb Ex db IIC T5 Gb Ex ia IIC T6 Ga Ex ia IIC T6...T5 Ga Ex mb IIC T6 Ex nA IIC T5 X Gc
Type of (ignition) protection for dust
Ex ia IIIB T135°C Da Ex mb tb IIIC T80°C Ex t IIIC T80°C Db Ex tb IIIC T100°C Db Ex tb IIIC T135°C Db Ex tc IIIC T95°C X Dc
Explosive ambient temperature
-20°C <= Ta <= +50°C -20°C <= Ta <= +60°C -40°C <= Ta <= +50°C -40°C <= Ta <= +65°C -65°C <= Ta <= +40°C -65°C <= Ta <= +55°C
Degree of protection
IP65 IP66 IP67 With plug socket as per IEC 60529
Exhaust air function
With flow control option
Sealing principle
Soft
Mounting position
Any
Conforms to standard
VDI/VDE 3845 (NAMUR)
Manual override
Detenting None Non-detenting Covered
Type of control
Pilot-controlled
Pilot air supply port
Internal
Flow direction
Non-reversible
Symbol
00991005 00991018 00991021 00991080 00991082 00991083 00991728 00991831 00991953 00995701
Lap
Overlap Underlap
Signal status display
With accessories
b-value
0.4 0.5
C value
2.1l/sbar 5.6l/sbar
Standard nominal flow rate, exhaust air return 4->3
110l/min
Switching time off
6ms 120ms
On switching time
4ms 35ms
Changeover time
2ms 55ms
Duty cycle
100%
Coil characteristics
110/120 V AC: 50/60 Hz, initial power 2.7 VA, holding power 1.9 VA 110/120 V AC: 50/60 Hz, initial power 4.4 VA, holding power 3.3 VA 110/120 V AC: 50/60 Hz, initial power 5.2 VA, holding power 3.1 VA 110/120 V AC: 50/60 Hz, initial power 6.9 VA, holding power 3.1 VA 110 V AC: 50/60 Hz, initial power 7.7 VA, holding power 3.8 VA 120 V AC: 60 Hz, initial power 10.0 VA, holding power 6.8 VA 12 V DC: 2.8 W 12 V DC: 3.4 W 230/240 V AC: 50/60 Hz, initial power 3.9 VA, holding power 2.8 VA 230/240 V AC: 50/60 Hz, initial power 5.8 VA, holding power 4.6 VA 230 V AC: 50/60 Hz, initial power 10.0 VA, holding power 6.0 VA 230 V AC: 50/60 Hz, initial power 11.5 VA, holding power 8.0 VA 230 V AC: 50/60 Hz, initial power 6.2 VA, holding power 3.7 VA 230 V AC: 50/60 Hz, initial power 6.9 VA, holding power 4.1 VA 24 V DC: 0.8 W 24 V DC: 2.1 W 24 V DC: 2.7 W 24 V DC: 3.3 W 24 V DC: 4.6 W 24 V AC: 50/60 Hz, initial power 2.5 VA, holding power 1.7 VA 24 V AC: 50/60 Hz, initial power 3.9 VA, holding power 2.6 VA 24 V DC: 0.7 W 24 V DC: 1.2 W 24 V DC: 2.6 W 48 V AC: 50/60 Hz, initial power 2.5 VA, holding power 1.7 VA 48 V AC: 50/60 Hz, initial power 3.9 VA, holding power 2.7 VA 48 V DC: 2.8 W 48 V DC: 3.4 W See solenoid coil, to be ordered separately
Permissible voltage fluctuations
+/- 10 %
Explosion prevention and protection
Class I, Div. 1 (US) Class I, Div. 2 (US) Class II, Div. 1 (US) Class II, Div. 2 (US) Class III, Div. 1 (US) Class III, Div. 2 (US) Observe the information on the certificate Zone 0 (IEC-EX) Zone 0 (KR) Zone 1 (ATEX) Zone 1 (IEC-EX) Zone 1 (KR) Zone 2 (ATEX) Zone 2 (KR) Zone 20 (IEC-EX) Zone 21 (ATEX) Zone 21 (IEC-EX) Zone 21 (KR) Zone 22 (ATEX) Zone 22 (KR)
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4]
Information on operating and pilot media
Operation with oil lubrication possible (required for further use)
Corrosion resistance class (CRC)
2 - Moderate corrosion stress
LABS (PWIS) conformity
VDMA24364-B2-L VDMA24364 zone III
Temperature of medium
-20°C 60°C
Ambient temperature
-20°C 60°C
Product weight
335g 685g
Electrical connection
3-pin Form A Form B Cable connector M20x1.5 M12x1, A-coded as per EN 61076-2-101 Plug as per EN 175301-803 As per industrial standard (11 mm)
Type of mounting
With through-hole
Venting hole connection
Not ducted
Pneumatic connection 1
G1/4 1/4 NPT QS-6 QS-8 QS-10 QS-1/4 QS-5/16 QS-3/8
Pneumatic connection 2
NAMUR connection diagram
Pneumatic connection 3
G1/4 1/4 NPT QS-6 QS-8 QS-10 QS-1/4 QS-5/16 QS-3/8
Pneumatic connection 4
NAMUR connection diagram
Pneumatic connection 5
G1/4 1/4 NPT QS-6 QS-8 QS-10 QS-5/16 QS-1/4 QS-3/8
Note on materials
RoHS-compliant
Seals material
NBR
Housing material
Wrought aluminum alloy
Material of screws
Steel, galvanized
Manufacturer ID
8026033

Specifications may be subject to change without notice