Product Model

ELR 1/35-600

In Stock
Last updated: 2025/4/18
Phoenix Contact ELR 1/35-600

Selling Points

  • 1High Load Capacity: Handles heavy loads with advanced technology for seamless operation.
  • 2Versatile Application: Ideal for controlling motors, pumps, and other electrical equipment.
  • 3Durable Construction: Built with high-quality materials for long-lasting performance.
  • 4Efficient Performance: Ensures reliable and efficient operation in industrial settings.
  • 5Advanced Technology: Features cutting-edge design with vibrant green color for a modern look.
Product Details
ELR 1/35-600
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Solid-state contactor
Operating mode
100% operating factor
Number of phases
1
Mains type
1-phase
Test voltage input/output
4 kV
Input name
Device supply
Typical response time
10 ms
Typical turn-off time
10 ms
Status display
LED (green)
Nominal output voltage
600 V AC
Nominal output voltage range
48 V AC ... 660 V AC
Peak offstate voltage
1200 V (Periodic peak reverse voltage)
Mains frequency
50 Hz 60 Hz
Continuous load current
35 A (see derating curve)
Load current
min. 100 mA
Leakage current
8 mA
Residual voltage
1.6 V
Surge current
750 A (t = 8.33 ms, at 25 °C)
Max. load value
1200 A
Protective circuit
RC element; RC element Surge protection
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Width
45 mm
Height
98 mm
Depth
105 mm
Color
green (RAL 6021)
Ambient temperature (operation)
-20 °C ... 80 °C
Standards/regulations
EN 61000-4-4 EN 61000-4-5
Assembly note
Can be aligned with > 40 mm spacing
Mounting position
Panel mounting on horizontal DIN rail

Specifications may be subject to change without notice