Product Model
ELR H3-I-SC-230AC/500AC-0,6

Selling Points
- 1Starts 3-phase AC motors up to 550V AC.
- 2Ensures safe operation with customizable overload protection.
- 3Ideal for DIN rail mounting with dimensions 22.5mm x 107mm x 114mm.
- 4230V AC input, 0.6A output current, and surge protection.
- 5Meets IP20 protection standards and operates in -25°C to 70°C ambient temperatures.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product type | Hybrid motor starters | Product family | CONTACTRON |
Operating mode | 100% operating factor | Article revision | 05 |
Number of phases | 3 | Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation for nominal condition | 0.4 W | Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation | 2.9 W | Minimum power dissipation | 2.6 W |
Coordination type | 1 | Rated control circuit supply voltage U | 230 V AC |
Control supply voltage range | 85 V AC ... 253 V AC | Rated control supply current I | 4 mA |
Mains frequency | 50/60 Hz | Protective circuit | Surge protection |
Rated insulation voltage | 500 V | Rated surge voltage | 4 kV |
Overvoltage category | III | Degree of pollution | 2 |
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC | Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Input name | Control input | Rated actuating voltage U | 230 V AC |
Triggering voltage range | 85 V AC ... 253 V AC | Rated actuating current I | 7 mA (Input type 1) |
Mains frequency | 50 Hz 60 Hz 50/60 Hz | Switching threshold | 44 V AC (“0” signal)
85 V AC (“1” signal) |
Typical turn-off time | < 70 ms | Rated operating voltage U | 500 V AC |
Operating voltage range | 42 V AC ... 550 V AC | Rated operating current I | 0.6 A (AC-51)
0.6 A (AC-53a) |
Mains frequency | 50/60 Hz | Load current range | 75 mA ... 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A | Cooling time | 20 min (for auto reset) |
Leakage current | 0 mA | Protective circuit | Surge protection |
Note | Confirmation: floating change-over contact, signal contact | Contact switching type | 1 changeover contact |
Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15)
2 A (24 V, DC13) | Connection method | Screw connection |
Stripping length | 8 mm | Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 | Tightening torque | 0.5 Nm ... 0.6 Nm
5 lb |
Connection method | Screw connection | Stripping length | 8 mm |
Screw thread | M3 | Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm
5 lb | Status display | LED (yellow) |
Operating voltage display | Green LED | Error indication | Red LED |
Width | 22.5 mm | Height | 107 mm |
Depth | 114 mm | Flammability rating according to UL 94 | V0 (Housing) |
Degree of protection | IP20 | Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C | Certificate | NLDX.E228652 |
SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) | FLA | 0.6 A (500 V AC) |
Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) | Category code | NLDX / NRNT |
Standards/regulations | IEC 60947-1
IEC 60947-4-2
IEC 61508
ISO 13849 | Mounting type | DIN rail mounting |
Assembly note | alignable, for spacing see derating | Mounting position | vertical (horizontal DIN rail, motor output below) |
Specifications may be subject to change without notice