Product Model

ELR H51-IES-24DC500AC-9-IOL

In Stock
Last updated: 2025/4/17
Phoenix Contact ELR H51-IES-24DC500AC-9-IOL

Selling Points

  • 1Short-circuit-proof design ensures reliable operation in harsh environments.
  • 2Emergency stop function provides immediate shutdown for safety.
  • 3Adjustable overload shutdown allows for customizable protection settings.
  • 424 V DC input with 9 A output current for efficient control.
  • 5SIL 3/PL e safety rating meets high standards for safety and reliability.
Product Details
ELR H51-IES-24DC500AC-9-IOL
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Hybrid motor starters
Product family
CONTACTRON
Operating mode
100% operating factor
Article revision
02
Number of phases
3
Motor starter type
Reversing starter
Switching frequency
≤ 2 Hz (Load-dependent)
Switching frequency
≤ 2 Hz (Load-dependent)
Maximum power dissipation
7 W
Minimum power dissipation
0.88 W
Coordination type
1
Rated control circuit supply voltage U
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current I
65 mA
Protective circuit
Surge protection Reverse polarity protection; Parallel polarity protection diode
Nominal voltage for I/O supply
24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.)
Current consumption
typ. 65 mA ±15 % (24 V DC) max. 150 mA
Protective circuit
Reverse polarity protection Short-circuit protection Overload protection
Rated insulation voltage
550 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
Safe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Operate threshold
> 60 A
Response time
< 0.5 s
Input name
Enable input
Rated actuating voltage U
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Rated actuating current I
7 mA
Switching threshold
9.6 V (“0” signal) 19.2 V (“1” signal)
Switching level
< 5 V DC (For EMERGENCY STOP)
Typical turn-off time
< 30 ms
Number of ports
1
Connection method
COMBICON
Connection technology
3-conductor
Specification
V1.1.1
Reverse polarity protection
yes
Cycle Time
30 ms
Amount of process data
8 Byte (Input data) 2 Byte (Output data)
Rated operating voltage U
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current I
9 A (AC-51) 7 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min (for auto reset)
Leakage current
0 mA
Protective circuit
Surge protection; Varistor
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm 5 lb
Status display
LED (yellow)
Operating voltage display
Green LED
Error indication
Red LED
Width
22.5 mm
Height
160 mm
Depth
114.5 mm
Flammability rating according to UL 94
V0 (Housing)
Degree of protection
IP20
Ambient temperature (operation)
-5 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m
Certificate
UKCA-compliant
Standards/regulations
IEC 60947-1 EN 60947-4-2 IEC 61508 ISO 13849-1
Assembly note
alignable, for spacing see derating
Mounting position
vertical (horizontal DIN rail, motor output below)