Product Model

ELR H5-ES-SC-230AC/500AC-2

In Stock
Last updated: 2025/4/19
Phoenix Contact ELR H5-ES-SC-230AC/500AC-2

Selling Points

  • 1Hybrid Motor Starter for Reversing 3~ AC Motors: Efficiently controls motors up to 500 V AC.
  • 2Adjustable Overload Shutdown: Ensures safe operation with customizable overload protection.
  • 3Emergency Stop Function to SIL 3/PL e: Meets high safety standards with SIL 3 and PL e certification.
  • 4Safe Isolation and Surge Protection: Provides reliable insulation and surge protection for enhanced safety.
  • 5Compact Design with Screw Connection: Space-saving design with easy screw connection for reduced wiring.
Product Details
ELR H5-ES-SC-230AC/500AC-2
Phoenix Contact

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product type
Hybrid motor starters
Product family
CONTACTRON
Operating mode
100% operating factor
Insulation
safe isolation
Number of phases
3
Service life electrical
3x 10
Reversing frequency
≤ 2 Hz
Maximum power dissipation
4.7 W
Minimum power dissipation
2.6 W
Coordination type
1
Rated insulation voltage
500 V
Rated surge voltage
6 kV
Rated control circuit supply voltage U
230 V AC
Control supply voltage range
92 V AC ... 253 V AC
Rated control supply current I
4 mA
Mains frequency
50/60 Hz
Protective circuit
Surge protection
Rated actuating voltage U
230 V AC
Triggering voltage range
92 V AC ... 253 V AC
Mains frequency
50 Hz 60 Hz 50/60 Hz
Switching threshold
44 V AC (“0” signal) 85 V AC (“1” signal)
Switching level
< 5 V AC (For EMERGENCY STOP)
Typical turn-off time
< 70 ms
Rated operating voltage U
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current I
2.4 A (AC-51) 2.4 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
180 mA ... 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min (for auto reset)
Leakage current
0 mA
Residual voltage
< 0.3 V
Protective circuit
Surge protection
Note
Confirmation 01: floating changeover contact
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section rigid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Status display
LED (yellow)
Operating voltage display
Green LED
Error indication
Red LED
Width
22.5 mm
Height
107 mm
Depth
114 mm
Flammability rating according to UL 94
V0 (Housing)
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Identification
≤ 3
Note
Safe shutdown
Identification
e
Note
Safe shutdown
Identification
≤ 3
Note
Safe shutdown
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) 5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
2.4 A (480 V)
Standards/regulations
DIN EN 50178 EN 60947
Standards/regulations
DWR 1300/ZXX01/DD/7080.8d
Standards/regulations
DIN EN 50178
Assembly note
Can be aligned with spacing = 20 mm
Mounting position
Vertical (horizontal DIN rail)

Specifications may be subject to change without notice